Chapter 1
ETERNUS DX Installation
This chapter explains the installation of the ETERNUS DX.
1.1 Installation Specifications
The following table shows the installation specifications of the ETERNUS DX.
Table 1.1 Installation Specifications
Item
ETERNUS DX60 S3
Dimensions (W ´
D ´ H)
Controller enclosure 2.5" type
482 ´ 645 ´ 88mm (2U)
3.5" type
482 ´ 670 ´ 88mm (2U)
Drive enclosure 2.5" type
482 ´ 540 ´ 88mm (2U)
3.5" type
482 ´ 560 ´ 88mm (2U)
Power distribution unit 1U
435 ´ 148 ´ 38mm
2U
(485 ´ 280 ´ 43mm) ´ 2 (*1)
Maximum weight
(*2)
Controller enclosure 2.5" type 35kg
3.5" type 35kg
Drive enclosure 2.5" type 35kg
3.5" type 35kg
Power distribution unit 1U 2kg
2U
(6kg) ´ 2 (*1)
Power Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
Maximum power
consumption (*2)
Controller enclo-
sure
2.5" type AC 100 – 120V 610W (620VA)
AC 200 – 240V 600W (610VA)
3.5" type AC 100 – 120V 530W (540VA)
AC 200 – 240V 530W (540VA)
Drive enclosure 2.5" type AC 100 – 120V 430W (440VA)
AC 200 – 240V 430W (440VA)
3.5" type AC 100 – 120V 340W (350VA)
AC 200 – 240V 340W (350VA)
10
FUJITSU Storage ETERNUS DX60 S3 Disk storage system Site Planning Guide
Copyright 2015 FUJITSU LIMITED
P3AM-8982-03ENZ0