Installation Methods
Perform one of the following rack installation methods to ensure the safe use of an ETERNUS DX
that is instal-
led in a rack:
-
To secure a rack, use a rack without stabilizers and secure it to the building with the leveling feet.
-
If a rack is not to be secured, make sure to use a rack with stabilizers and use these stabilizers to prevent the
rack from toppling over.
Which installation method should be used depends on the installation location, the floor conditions, and the
type of racks that are to be used. Contact your installation contractor for more details regarding installation
and how the installation should actually be performed.
An installation diagram when installing a rack (or the floor dimensions of the rack) is shown below.
19-inch Racks (with Standard Door, 2000mm)
Figure 15 Floor Dimensions of the Rack (of 19-inch Racks (with Standard Door, 2000mm))
919mm (leveling feet)
733mm (caster)
Front Rear
523mm
(caster)
350mm
570mm
(leveling feet)
175mm
700mm
1,050mm
95mm
826mm
65mm
89
mm
47mm
140mm
1,013mm
Caster
Leveling feet
Cable slot
1. ETERNUS DX Installation
Installation Environment
33
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems
Site Planning Guide
Copyright 2020 FUJITSU LIMITED
P3AM-9422-13ENZ0