EasyManua.ls Logo

Fujitsu Eternus DX90 S2 - Chapter 3 Configuration Settings and Display; 3.1 Thin Provisioning Pool Management

Fujitsu Eternus DX90 S2
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Rack and Optional Product Installation
4.3 Standard Installation Rules Before Shipment (Only for Regions Other than EMEA&I)
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED P3AM-4822-12ENZ0
69
Table 4.2 Specifications for the unit installation area
â–  Placement conditions
When determining service areas, refer to the installation document of the rack to be used.
Install air conditioning in order to ensure that the interior temperature of the rack satisfies the temperature
conditions listed in "2.1 Installation Specifications" (page 27)
and "2.5.1 Air Conditioning" (page 36).
4.3 Standard Installation Rules Before Shipment
(Only for Regions Other than EMEA&I)
This section explains the rules for combining the following optional products and standard installation rules
that apply before shipment from the factory.
• Host interfaces
• Drive enclosures
• Drives
Specification Condition
(1) Rack front space
(Space between the fixed part of the ETERNUS DX Disk storage system on
the front side and the front of the rack)
40mm or more
(2) Mount bracket length
(Size between each end of the front and rear rack pillars)
685mm to 775mm
(3) Rack space
(Space between the fixed part of the ETERNUS DX Disk storage system on
the front side and the rear of the rack)
830mm or more
(4) Rack mount kit installation area 482mm or more
(recommended)