7. Additional charge calculation
7-1. Model: AOHG18KBTB
Refrigerant type R32
Refrigerant amount g 1,020
¢ Refrigerant charge
Total pipe length m 20 or less 25 30 (Max.)
20 g/m
Additional charge g 0 100 200
7-2. Models: AOHG22KBTB and AOHG24KBTB
Refrigerant type R32
Refrigerant amount g 1,250
¢ Refrigerant charge
Total pipe length m 20 or less 25 30 (Max.)
20 g/m
Additional charge g 0 100 200
7-3. Models: AOHG30KBTB and AOHG36KBTB
Refrigerant type R32
Refrigerant amount g 1,900
¢ Refrigerant charge
Total pipe length m 30 or less 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800
7-4. Model: AOHG45KBTB
Refrigerant type R32
Refrigerant amount g 2,700
¢ Refrigerant charge
Total pipe length m 30 or less 40 50 (Max.)
40 g/m
Additional charge amount g 0 400 800