8-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart
8-7. Low outdoor temperature protection
→hen the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode Cooling/Dry
Trigger condition -15°C
Release condition -10°C
8-8. High temperature and high pressure release control
(heating mode)
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB: 63°C
BC: 55°C
CD: 53°C
DE: 50°C
Zone Operation
Zone A Compressor is stopped.
Zone B
The rotation number of compressor is decreased.
-25 rps/120 sec.
Zone C -3 rps/60 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E