6.3 Preparations for Use
– Be careful of injuries during installation of the PRIMEPOWER400 Rackmount (10U)
Server into the rack.
– Do not install the PRIMEPOWER400 Rackmount (10U) Server into a rack if the server
unit may make the entire rack unstable.
– Maximum configured weight of this unit: 102 kg (225.17 lb.)
If the PRIMEPOWER400 Rackmount (10U) Server is supplied with power from a power strip
or service outlet of other units, it may overload the power supply cord or the power strip of
other units.
– Confirm that the current rating of the power strip or service outlet exceeds the combined
ratings of all equipment it is supplying.
– Electrical ratings of this unit: 100 to 240VAC, 12.0A to 6.0A, 50/60Hz, single-phase
Reliable earthing of rack-mounted equipment should be maintained. Particular attention should
be given to non-direct-to-mains connections (e.g. via power strips, etc.).
CAUTION
Connect the ground before connecting any of the power supply
lines. If all of the power cables from the Expansion File Unit Type-2
are connected to a single power strip, high leakage current
exceeding the stipulated value may leak through to the earth lead
of the power strip.
If the power strip is not directly connected to the main distribution
panel, use a power strip with an industrial plug.
General installation notes
Do not block the ventilation holes.
Do not install the PRIMEPOWER400 Rackmount (10U) Server where it will be exposed to
sunlight or sources of heat.
Do not install the PRIMEPOWER400 Rackmount (10U) Server in dusty places or places where
it will be exposed to corrosive gases or sea breezes.
Keep the PRIMEPOWER400 Rackmount (10U) Server isolated from vibration. Install the
PRIMEPOWER400 Rackmount (10U) Server on a level surface so that it does not tilt.
Make sure that the AC power supply source is grounded properly using a maximum resistance
of 100 Ohms. Also, do not ground the AC power supply source using a shared ground. Use
only an independent grounding point. Otherwise, the PRIMEPOWER400 Rackmount (10U)
Server may malfunction.
Do not run a cable under a unit or allow a cable to become taut. Do not disconnect the power
cable when the power is on.
Do not place anything on the PRIMEPOWER400 Rackmount (10U) Server. Do not use the top
of the PRIMEPOWER400 Rackmount (10U) Server as a workspace.
To prevent condensation in the PRIMEPOWER400 Rackmount (10U) Server, do not raise the
ambient room temperature rapidly in winter.
Use the PRIMEPOWER400 Rackmount (10U) Server only after it has warmed up sufficiently.
97