Chapter 4 FRU Removal Preparation 4-5
4.2.2 Disconnecting and Replacing a FRU
1. From the XSCF Shell prompt, use the replacefru command:
Note – DDC_A is displayed only for the M8000.
The command is menu-driven. The example continues using a FAN unit.
The replacefru command will automatically test the status of the component after
the disconnecting off and replace has finished.
XSCF> replacefru
----------------------------------------------------------------
Maintenance/Replacement Menu
Please select a type of FRU to be replaced.
1. CMU/IOU(CPU Memory Board Unit/IO Unit)
2. FAN(Fan Unit)
3. PSU(Power Supply Unit)
4. XSCFU(Extended System Control Facility Unit)
5. DDC_A(DDC for BP_A)
----------------------------------------------------------------
Select [1-5|c:cancel] :
Select [1,2|c:cancel] :1
---------------------------------------------------
Maintenance/Replacement Menu
Please select a FAN to be replaced.
No. FRU Status
--- --------------- ------------------
1. FAN_A#0 Normal
2. FAN_A#1 Normal
3. FAN_A#2 Normal
4. FAN_A#3 Normal
---------------------------------------------------
Select [1-4|b:back] :1
You are about to replace FAN_A#0.
Do you want to continue?[r:replace|c:cancel] :r
Please confirm the Check LED is blinking.
If this is the case, please replace FAN_A#0.
After replacement has been completed, please select[f:finish] :f