- 14 -
Line Function
Setting range
or display
Setting
increment
Basic
setting
Holidays, heating circuit 2 (For the Holiday program is active, the heating mode should be on AUTO).
If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option).
651 Preselection Period 1 to 8 Period 1
652 Period Start (Day / Month) 01.01... 31.12 1
653 Period End (Day / Month) 01.01... 31.12 1
658 Operating level Frost protection, Reduced Frost
protection
Heating adjustment, circuit 1
710 Comfort setpoint Reduced setpoint…
Comfort setpoint maximum
0,5 °C 20 °C
712 Reduced setpoint Frost protection setpoint…
Comfort setpoint
0,5 °C 19 °C
714 Frost protection setpoint 4 °C… Reduced setpoint 0,5 °C 8 °C
Cooling circuit 1
If the installation is tted with the cooling kit (Only with the cooling kit option).
901 Operating mode Protection, Automatic, Reduced,
Comfort
Protection
902 Comfort cooling setpoint 17... 40 °C 0,5 °C 24 °C
903 Reduced setpoint 5... 40°C 26 °C
Heating adjustment, Circuit 2
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
1010 Comfort setpoint Reduced setpoint…
Comfort setpoint maximum
0,5 °C 20 °C
1012 Reduced setpoint Frost protection setpoint…
Comfort setpoint
0,5 °C 19 °C
1014 Frost protection setpoint 4 °C… Reduced setpoint 0,5 °C 8 °C
Cooling circuit 2
If the installation is tted with the cooling kit (Only with the cooling kit option).
1201 Operating mode Protection, Automatic, Reduced,
Comfort
Protection
1202 Comfort cooling setpoint 17... 40 °C 0,5 °C 24 °C
1203 Reduced setpoint 5... 40°C 26 °C
Domestic hot water
If the installation is tted with the DHW kit.
1600 Operating mode O󰀨, On, Eco On
1610 Nominal setpoint Reduced setpoint (line 1612)…
65 °C
1 55 °C
The backup electrical system is required to reach this level.
1612 Reduced setting 8 °C...
Nominal setting (line 1610)
1 40 °C
Swimming pool (Only with swimming pool kit option)
2055 Setpoint solar heating 8... 80 °C 26 °C
2056 Setpoint source heating 8... 35 °C 22 °C
Waterstage / OPERATING INSTRUCTIONS / 2010 - EN