- 23 -
g. 24 - Section of the opening
Room volume (m
3
) 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5
Refrigerant Amount (g) Minimal section (S) of the opening (cm
2
)
970 500 350 250 200 200
1000 550 350 300 250 200
1100 600 400 300 250 200 200
No requirement
1170 600 400 300 250 200 200
1300 700 450 350 300 250 200 200
1400 750 500 400 300 250 250 200 200
1500 800 550 400 350 300 250 200 200 200
1600 850 550 450 350 300 250 250 200 200
1700 900 600 450 350 300 250 250 200 200 200
1800 950 650 500 400 350 300 250 250 200 200 200
1840 950 650 500 400 350 300 250 250 200 200 200
g. 25 - Position of openings for ventilation

200max
S
S
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN