- 48 -
Controller Menu
▼
General
Only the parameters accessible at the levels:
U - end user.
I - Commissioning
S - Engineering.
are described in this document.
The access levels are specifi ed in the second column of
the table by means of the letters U, I and S.
The OEM parameters are not described and require a
manufacturer access code.
▼
Setting parameters
- Selecting the desired level.
- Scroll the list of menus.
- Selecting the desired menu.
- Scroll the function lines.
- Selecting the desired line.
- Adjusting the parameter.
- Validate the setting by pressing OK.
- To return to the menu, press ESC.
If no setting is made for 8 minutes, the screen
automatically returns to the basic display.
OK
Press and release
End user
O
OK OK
Time of day and date Hours / minutes 1 Time 1...24 h
User interface Day/Month 2 Minutes 0...60 min
Heating circuit 1 timer
programme
Year 3
...
Press for 3
seconds
End user Start-up Specialist OEM
Time of day and date
Hours / minutes 1
User interface
Day/Month 2
Heating circuit 1 timer
programme
Year 3
...
End date of summer time 4 01.01...31.12
End date of summer time 5
▼
Recommended settings for the parameters depending on the installation's emitters
Very Low Temperature
Radiators /
Heating-cooling fl oor
Low temperature
radiators
Dynamic radiators or
fan-coil heaters
Classic
temperature
radiators
Heating curve
slope
720 (CC1)
0.25 to 0.5 0.5 to 1.25 0.4 to 1.1 1.25 to 3
1020 (CC2)
Curve
displacement
721 (CC1)
0040
1021 (CC2)
Flow temp
setpoint Min
740 (CC1)
Factory (17°C) Factory (17°C) 30 or 35°C Factory (17°C)
1040 (CC2)
Flow temp
setpoint Max
741 (CC1)
50°C Factory (60°C) 65°C 65°C
1041 (CC2)
DHW charging
time limitation
5030 Factory (90 min) Factory (90 min) 40 min Factory (90 min)