- 52 -
Line Function
Setting range
or display
Setting
increment
Basic
setting
850 I Floor curing function ( g. 51) O
- O : Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends automatically
after 25 days.
Please comply with the
standards and instructions
of the manufacturer of the
building ! A good performance
of this function is only possible
with an installation correctly
implemented (hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting the
adjustment on "O ".
50
45
40
35
30
20
25
55
X
01 5 10 181
57
1
25
g. 51 - Diagram of the concrete slab drying programmes
Heating ow temperature °C
Operational heating + Heating ready for occupation
Heating ready for occupation
Day
Operational
heating
851 I Floor curing setpoint manually
(if line 850 = manual)
0... 95 °C 1 °C 25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains xed.
The concrete slab-drying programme stops automatically after running for 25 days.
856 I Floor curing day current 0... 32 0
857 I Floor curing day completed 0... 32 0
900 S Operating mode changeover None, Protection mode,
Reduced, Comfort, Automatic
1 Reduced
Operating mode at end of concrete slab drying period
Cooling circuit 1
If the installation is tted with the cooling kit (Only with the cooling kit option).
901 U Operating mode Protection, Automatic, Reduced,
Comfort
Protection
902 U Comfort cooling setpoint 5... 40 °C 0.5 °C 24 °C
903 U Reduced setpoint 5... 40°C 26 °C
908 I Flow temp setp at OT° 25°C 6... 35 °C 0.5 °C 20 °C
909 I Flow temp setp at OT° 35°C 6... 35 °C 0.5 °C 16 °C
912 I Cooling limit at OT° --, 8... 35 °C 0.5 °C 24 °C
913 S Lock time at end of heating / cooling --, 8... 100 1 h 24 h
918 S Summer comp start at OT° 20... 50 °C 1 °C 26 °C
919 S Summer comp end at OT° 20... 50 °C 1 °C 40 °C
920 S Summer comp setp increase --, 1... 10 °C 1 °C 4 °C
923 S Flow temp setp min OT° 25°C 6... 35 °C 0.5 °C 18 °C
924 S Flow temp setp min OT° 35°C 6... 35 °C 0.5 °C 18 °C
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN