Split system (Single phase and 3-phase type)
34 Maintenance Document 1544-1
Clear 39: Abnormal noise
Probable causes:
Abnormal installation (outdoor)
Fan failure
Compressor failure.
Checks:
1. The noise comes from the outdoor unit:
- Is the unit stable?
- Is the protection screen properly mounted?
- Is the propeller broken or distorted?
- Has the propeller screw been lost?
- Is any object blocking the propeller rotation?
OK
- Check for any vibration noise caused by a
bolt.
- Check for any sound of contact with a pipe.
OK
- Is the compressor locked?
OK