Split system (Single phase and 3-phase type)
Maintenance Document 1544-1 49
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
920 S Summer comp setp increase ---/1…10°C 4°C
923 S Flow temp setp min OT 25°C 6…35°C 18°C
924 S Flow temp setp min OT 35°C 6…35°C 18°C
928 S Room influence ---/1…100% 80%
932 S Room temp limitation ---/0…4°C 0.5°C
938 S Mixing valve decrease 0…20°C 0°C
941 S Actuator running time 30…650s 120s
945 S Mixing valve in heating mode
Control ¦ Open
Open
963 S With prim contr/system pump
No ¦ Yes
No
Heating circuit 2
1010 U Comfort setpoint
Reduced temp to
35°C
20°C
1012 U Reduced setpoint 19°C
1014 U Frost protection setpoint
4°C to Reduced
temp
8°C
1016 S Comfort setpoint maximum 20…35°C 28°C
1020 I Heating curve slope 0,1…4 0,5
1021 I Heating curve displacement
-4,5°C…4,5°C
0°C
1026 S Heating curve adaption Off, on Off
1030 I Summer/winter heating limit 8°C…30°C 18°C
1032 S 24-hour heating limit -10°C…10°C -2°C
1040 S
Flow temp setpoint min (for fan
convectors)
8°C… 95°C 8°C
1041 I Flow temp setpoint max 8°C… 95°C 55°C
1050 I Room influence 1%...100% 50%
1080 S Quick setback
Off ¦ Down to reduced
setpoint ¦ Down to frost
prot setpoint
Down to reduced
setpoint
1090 S Optimum start control max 0…360min 180 min
1091 S Optimum stop control max 0…360min 60 min
1100 S Reduced setpoint increase start -30…10°C ---
1101 S Reduced setpoint increase end -30…10°C -5°C
1130 S Mixer valve boost 0…50°C 0°C
1134 S Actuator running time 30…873s 240s
1150 I Floor curing function Off
1151 I Floor curing setpoint manually 0°C…95°C 25°C
1156 I Floor curing day current 0…32
1157 I Floor curing day completed 0…32 0
1200 S Optg mode changeover
Protection mode
Domestic hot water
1610 U Nominal setpoint Thc…65°C 55°C
1612 U Reduced setpoint 8°C….Thc 40°C
1620 I Release of DHW load
24h/day
Heating circ time pgms
Time program 4/DHW
Off-peak rate
4: Time pgm 4/DHW or
Off-peak rate
Time program
4/DHW
1640 I Legionella function
Off
Periodically
Fixed weekday
Off
1641 I Legionella function periodically 1 to 7 7
1642 I Legionella function weekday Mon,…Sun Sunday
Swimming pool
2056 U Setpoint source heating 8…80 22
Heat pump
2803 S Overrun time cond pump 0…240s 240
2843 S Compressor off time min 0…120min 8min
2844 S Switch-off temp max 8°C… 100°C 75°C
2862 S Locking time stage 2 0…40min 5min