Split system (Single phase and 3-phase type)
Maintenance Document 1544-1 61
Important
o The standards and directions of the building
contractor must be followed!
o This function will not work properly unless the
installation has been adequately made (hydraulics,
electricity, settings). Otherwise, the floors to be dried
may be damaged!
o The function may be prematurely interrupted
by setting it to Off.
o The maximum flow temperature limitation
remains active.
Floor curing setpoint manually
The flow temperature setpoint for the "Manual"
controlled floor drying function can be adjusted
separately for each heating circuit.
Floor curing day current
Displays the current flow temperature setpoint for the
controlled floor drying function
Floor curing day completed
Displays the current day of the controlled floor drying
function
Important:
After a power outage, the installation resumes the
controlled drying function as it was when the outage
occurred.
Operating Mode Changeover
Line no.
HC1 HC2
Programming line
900 1200 Optg mode changeover
(None / Frost protection mode / Reduced / Comfort / Automatic)
In case of an external changeover via input H2 (on the extension module only) the operating mode to which the
changeover will be performed must be previously defined.
Heating Circuit Frost Protection
The heating circuit frost protection is continuously
activated (protection mode
) and is not adjustable.
Heating circuit frost protection in heating mode
If the flow temperature is below 5°C, the controller
initiates the production of heat and starts the heating
pumps, regardless of the current heating mode.
If the flow temperature rises again above 7°C, the
controller waits another 5 minutes, and then stops the
production of heat and the heating pumps.
Heating circuit frost protection in cooling mode
See Cooling mode
Days
Heat pump
flow tem
p
Fh
Bh
X : Starting day
Fh + Bh