- (OU01 - 06) -
Outdoor unit / 3 phase
OUTDOOR UNIT
WO
K112-160LC
OUTDOOR UNIT
WO
K112-160LC
ELECTRICAL SPECIFICATIONS2-3.
Model name (Outdoor unit) WO
Û
K112LCT WO
Û
K140LCT WO
Û
K160LCT
Available voltage range 342 - 457V
Power supply
Voltage V 3N~ 400V
Frequency Hz 50
*1) Max. operating current Heating
A
9.0 9.5 10.5
Starting current 4.3 5.5 6.5
*2) Wiring spec.
Main fuse (Circuit breaker) Current 16.0
Power cable mm² 2.5
Wiring connections
For power supply
*3) Quantity
5
For connection with indoor 4
*1) The maximum current is the total current of indoor unit and outdoor unit.
*2) Wiring spec. :
Selected sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*3) Included earth wiring.