- (CS01 - 75) -
Control system
- (CS01 - 75) -
CONTROL
SYSTEM
CONTROL
SYSTEM
In the case of 2 heating circuits
Choose the allocation of the remote control unit (room appliance 1 or 2…) line 40*. -
According to the allocation selected check and, if necessary, modify the settings for lines 42*, 44*, 48*. -
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
40 I Use as... Room appliance 1, 2, P,
User interface 1, 2, P,
Service appliance
Room
appliance 1
This line regulates the use of the room control unit. Depending on how it is used, other settings will be
necessary (lines 42, 44, 48).
42 I Appliance allocation 1 Heating circuit 1,
Heating circuit 1 & 2,
Heating circuit 1 & P,
All the heating circuits
Heating
circuit 1
44 I Operation HC2 (command HC2) Commonly with HC1,
Independent
Commonly
with HC1
This function enables you to choose whether you wish the room thermostat (as an option) to act on both
zones or just a single zone.
48 I Occupancy control switch function Without,
Heating circuit 1,
Heating circuit 2,
Common
* These parameter lines are only accessible from the remote control unit.