EasyManua.ls Logo

Fujitsu WOxK112LCT - Dimensions; Technical Specifications

Fujitsu WOxK112LCT
139 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- (OU01 - 05) -
Outdoor unit / 3 phase
OUTDOOR UNIT
WO
K112-160LC
OUTDOOR UNIT
WO
K112-160LC
TECHNICAL SPECIFICATIONS2-2.
Model name (Outdoor unit) WO
Û
K112LCT WO
Û
K140LCT WO
Û
K160LCT
Enclosure
Colour BEIGE (10YR 7.5/1.0)
Material Steel sheet
Dimensions
(H x W x D)
Net
mm
1290 x 900 x 330
Gross 1430 x 1050 x 445
Weight
Net
kg
99
Gross 107
Heat exchanger type
Dimensions (H x W x D)
mm
1260 x 900 x 36.4
Fin pitch 1.3
Rows & Stages 2 x 60
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminium)
Surface treatment Corrosion resistance (Blue n)
Fan
Airow rate Heating m³/h 6200 6900
Type x Q'ty Propeller x 2
Discharge direction Horizontal
Motor Quantity 2
Motor output W 104
Compressor
Type x Q'ty DC 2 rotary (Liquid injection) x 1
Motor output W 3,750
Operation range
Heating
Min
°CDB
-25
Max 35
Sanitary
water
Min -25
Max 35
Sound pressure level Heating dBA 53 55 56
Refrigerant
Type R410A
Charge g 2,500
Control Expansion valve (electric type)
Nr of circuits 1
Refrigerant oil
Type VG74
Charged volume l 1.55
Connection pipe
Type
Liquid Flare connection
Gas Flare connection
Size
(Standard)
Liquid
mm
9.52
Gas 15.88
Drain
Type x Q'ty Socket x 3
Size mm 18
Pre-charge length
m
15
Max. length 20
Min. length 5
Additional refrigerant charge g/m 50
Max. height difference m 15
Defrost method Reverse cycle
Defrost control Outdoor heat exchanger temperature sensor
Capacity control method Inverter control

Table of Contents