output current rating | 15 amperes for input voltages of 124V |
---|---|
initial turn-on voltage | 200V |
maximum surge current | 6, 500 amps |
regulation range | ±5V from 97V to 141V |
---|---|
shutdown range | below 75V or above 150V |
voltmeter accuracy | ±5V |
spike clamping voltage | 400 volts peak at 500 A |
---|---|
maximum spike energy | 80 joules per node; 240 joules total |
noise attenuation | 20 dB at 200 kHz, rising to >40 dB, 1 to 100 MHz |
dimensions | 1.75” H x 19” W x 8.5” D |
---|---|
weight | 12 lbs. (5.5 kg) |
output current rating | 15 amperes for input voltages of 124V |
---|---|
initial turn-on voltage | 200V |
maximum surge current | 6, 500 amps |
regulation range | ±4V from 82V to 115V |
---|---|
shutdown range | below 65V or above 135V |
voltmeter accuracy | ±4V |
spike clamping voltage | 400 volts peak at 500 A |
---|---|
maximum spike energy | 80 joules per node; 240 joules total |
noise attenuation | 20 dB at 200 kHz, rising to >40 dB, 1 to 100 MHz |
dimensions | 1.75” H x 19” W x 8.5” D |
---|---|
weight | 12 lbs. (5.5 kg) |
output current rating | 6 amperes for input voltages of 228V/238V/248V |
---|---|
initial turn-on voltage | 390 volts peak L-N; 680 volts peak N-G, L-G |
regulation range | ±10V in the following ranges: 174-264V (220 mode), 181-276V (230 mode), 190-288V (240 mode) |
---|---|
shutdown range | below 146V or above 279V (220 mode); below 152V or above 287V (230 mode), below 158V or above 300V (240 mode) |
voltmeter accuracy | ±10V |
spike clamping voltage | 400 volts peak at 500 A |
---|---|
maximum spike energy | 130 joules L-N, 160 joules N-G, L-G, 450 joules total |
noise attenuation | 20 dB at 200 kHz, rising to >40 dB, 1 to 100 MHz |
dimensions | 1.75” H x 19” W x 8.5” D |
---|---|
weight | 12 lbs. (5.5 kg) |