EasyManua.ls Logo

GE 469 - Default Assignments for User-Definable Memory Map Area

GE 469
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP COMMUNICATIONS GUIDE
The 469 provides default assignments for user map addresses #1 to #55, as shown below.
The User can change the user assigned addresses as per their requirement. To return to
these default assignments, use Enervista 469 Setup to set Modbus User Map – User Map –
Default.
Table 1: Default assignments for User-Definable Memory Map Area
USER MAP ADDRESS #
MODBUS
REGISTER
ADDRESS (HEX)
USER ASSIGNED
ADDRESS (HEX)
DESCRIPTION
User Map Address #1 0100 0200 Motor status
User Map Address #2 0101 0210 General status
User Map Address #3 0102 0211 Output relay status
User Map Address #4 0103 0227
Phase A pre-trip current (1st
word)
User Map Address #5 0104 0228
Phase A pre-trip current (2nd
word)
User Map Address #6 0105 0229
Phase B pre-trip current (1st
word)
User Map Address #7 0106 022A
Phase B pre-trip current (2nd
word)
User Map Address #8 0107 022B
Phase C pre-trip current (1st
word)
User Map Address #9 0108 022C
Phase C pre-trip current (2nd
word)
User Map Address #10 0109 02D0 Access switch status
User Map Address #11 010A 02D1 Test switch status
User Map Address #12 010B 02D2 Starter switch status
User Map Address #13 010C 02D3
Emergency restart switch
status
User Map Address #14 010D 02D4 Remote reset switch status
User Map Address #15 010E 02D9 Trip coil supervision
User Map Address #16 010F 0300 Phase A current (1st word)
User Map Address #17 0110 0301 Phase A current (2nd word)
User Map Address #18 0111 0302 Phase B current (1st word)
User Map Address #19 0112 0303 Phase B current (2nd word)
User Map Address #20 0113 0304 Phase C current (1st word)
User Map Address #21 0114 0305 Phase C current (2nd word)
User Map Address #22 0115 0306
Average phase current (1st
word)
User Map Address #23 0116 0307
Average phase current (2nd
word)
User Map Address #24 0117 030B Ground current (1st word)
User Map Address #25 0118 030C Ground current (2nd word)
User Map Address #26 0119 0321 RTD #1 temperature
User Map Address #27 011A 0322 RTD #2 temperature
User Map Address #28 011B 0323 RTD #3 temperature
User Map Address #29 011C 0324 RTD #4 temperature
User Map Address #30 011D 0325 RTD #5 temperature
User Map Address #31 011E 0326 RTD #6 temperature
User Map Address #32 011F 0327 RTD #7 temperature
User Map Address #33 0120 0328 RTD #8 temperature
User Map Address #34 0121 0329 RTD #9 temperature
User Map Address #35 0122 032A RTD #10 temperature

Table of Contents

Other manuals for GE 469

Related product manuals