11-114 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
Factory Service
Percent Differential 1
63000 0x59D7 Name 0 65535 1 F60_26 Percent Diff
1
26
63013 0x59E4 Function 0 4 1 FC100D 0 1
63014 0x59E5 Type 0 1 1 FC356 0 1
63015 0x59E6 Pickup 5 100 1 x CT F2 20 1
63016 0x59E7 Slope 1 1 100 1 % F0 25 1
63017 0x59E8 Break 1 50 200 1 x CT F2 150 1
63018 0x59E9 Break 2 200 3000 1 x CT F2 400 1
63019 0x59EA Slope 2 1 100 1 % F0 95 1
63020 0x59EB Pickup Delay 0 10000 1 s F3 0 1
63021 0x59EC Restraint Factor Starting 0 1000 1 F3 100 1
63027 0x59F2 Block 0 0xFFFFFFFF 1 FC142 0 1
63029 0x59F4 Relays 0 0xFFFFFFFF 1 FC198H 0 1
63037 0x59FC Events 0 1 1 FC126 1 1
63038 0x59FD Targets 0 2 1 FC101 2 1
Thermal Model
63110 0x5A45 Name 0 65535 1 F60_26 Thermal 26
63123 0x5A52 Trip Function 0 4 1 FC100D 0 1
63125 0x5A54 Overload Curve 16 23 1 FC161C 23 1
63126 0x5A55 Curve Effect 0 1 1 FC353 0 1
63127 0x5A56 Curve k Factor 100 150 5 F2 110 1
63128 0x5A57 IEC Curve Time Constant 0 1000 1 min F0 45 1
63129 0x5A58 TD Multiplier 0 2500 1 F2 100 1
63130 0x5A59 TD Multiplier 0 60000 1 F2 0 1
63131 0x5A5A Unbalance Bias K Factor 0 19 1 F0 0 1
63132 0x5A5B Cool Time Constant
Running
1 1000 1 min F0 15 1
63133 0x5A5C Cool Time Constant
Stopped
1 1000 1 min F0 30 1
63134 0x5A5D Hot/Cold Safe Stall Ratio 1 100 1 F2 100 1
63135 0x5A5E RTD Bias 0 1 1 FC126 0 1
63136 0x5A5F RTD Bias Minimum 0 250 1 °C F0 40 1
63137 0x5A60 RTD Bias Center Point 0 250 1 °C F0 130 1
63138 0x5A61 RTD Bias Maximum 0 250 1 °C F0 155 1
63139 0x5A62 Volt. Dependent (VD)
Function
011 FC12601
63140 0x5A63 VD Min Motor Volts 60 99 1 % F0 80 1
63141 0x5A64 VD Voltage Loss 0 0xFFFFFFFF 1 FC142 0 1
63143 0x5A66 VD Stall Current @ Min V 150 2000 1 x FLA F2 450 1
63144 0x5A67 VD Stall Time @ Min V 1 10000 1 s F1 200 1
63145 0x5A68 VD Accel. Intersect @ Min
V
150 2000 1 x FLA F2 400 1
63146 0x5A69 VD Stall Current @ 100%
V
150 2000 1 x FLA F2 600 1
63147 0x5A6A VD Stall Time @ 100% V 1 10000 1 s F1 100 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words