CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 11-115
63148 0x5A6B VD Accel. Intersect @
100% V
150 2000 1 x FLA F2 500 1
63149 0x5A6C Alarm Function 0 3 1 FC100E 0 1
63150 0x5A6D Alarm Pickup 1000 10000 100 % TC F2 7500 1
63151 0x5A6E Alarm Output Relays 0 0xFFFFFFFF 1 FC198C 0 1
63153 0x5A70 Trip Output Relays 0 0xFFFFFFFF 1 FC198D 0 1
63155 0x5A72 Block 0 0xFFFFFFFF 1 FC142 0 1
63157 0x5A74 Events 0 1 1 FC126 1 1
63158 0x5A75 Targets 0 2 1 FC101 2 1
Current Unbalance
63170 0x5A81 Name 0 65535 1 F60_26 Cur Unbal 26
63183 0x5A8E Trip Function 0 4 1 FC100D 0 1
63184 0x5A8F Trip Pickup 40 500 1 % F1 150 1
63185 0x5A90 Trip Pickup Delay 0 18000 1 s F2 100 1
63186 0x5A91 Trip Dropout Delay 0 18000 1 s F2 100 1
63187 0x5A92 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 1
63189 0x5A94 Alarm Function 0 3 1 FC100E 0 1
63190 0x5A95 Alarm Pickup 40 500 1 % F1 150 1
63191 0x5A96 Alarm Pickup Delay 0 18000 1 s F2 100 1
63192 0x5A97 Alarm Dropout Delay 0 18000 1 s F2 100 1
63193 0x5A98 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 1
63195 0x5A9A Block 0 0xFFFFFFFF 1 FC142 0 1
63197 0x5A9C Events 0 1 1 FC126 1 1
63198 0x5A9D Targets 0 2 1 FC101 1 1
Mechanical Jam
63210 0x5AA9 Name 0 65535 1 F60_26 Mech Jam 26
63223 0x5AB6 Function 0 4 1 FC100 0 1
63224 0x5AB7 Pickup 100 1000 1 x FLA F2 200 1
63225 0x5AB8 Pickup Delay 10 18000 1 s F2 100 1
63226 0x5AB9 Dropout Delay 0 18000 1 s F2 100 1
63227 0x5ABA Relays 0 0xFFFFFFFF 1 FC198 0 1
63229 0x5ABC Block 0 0xFFFFFFFF 1 FC142 0 1
63231 0x5ABE Events 0 1 1 FC126 1 1
63232 0x5ABF Targets 0 2 1 FC101 2 1
Undercurrent
63250 0x5AD1 Name 0 65535 1 F60_26 Undercur 26
63263 0x5ADE Trip Function 0 4 1 FC100D 0 1
63264 0x5ADF Start Block Delay 0 60000 1 s F2 50 1
63265 0x5AE0 Trip Pickup 10 95 1 x FLA F2 70 1
63266 0x5AE1 Trip Pickup Delay 0 18000 1 s F2 100 1
63267 0x5AE2 Trip Dropout Delay 0 18000 1 s F2 100 1
63268 0x5AE3 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 1
63270 0x5AE5 Alarm Function 0 3 1 FC100E 0 1
63271 0x5AE6 Alarm Pickup 10 95 1 x FLA F2 70 1
63272 0x5AE7 Alarm Pickup Delay 0 18000 1 s F2 100 1
63273 0x5AE8 Alarm Dropout Delay 0 18000 1 s F2 100 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words