11-116 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
63274 0x5AE9 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 1
63276 0x5AEB Block 0 0xFFFFFFFF 1 FC142 0 1
63278 0x5AED Events 0 1 1 FC126 1 1
63279 0x5AEE Targets 0 2 1 FC101 1 1
Overload Alarm
63500 0x5BCB Name 0 65535 1 F60_26 Overload 26
63513 0x5BD8 Function 0 4 1 FC100A 0 1
63514 0x5BD9 Pickup 50 300 1 x FLA F2 70 1
63515 0x5BDA Pickup Delay 0 18000 1 s F2 100 1
63516 0x5BDB Dropout Delay 0 18000 1 s F2 100 1
63517 0x5BDC Block 0 0xFFFFFFFF 1 FC142 0 1
63519 0x5BDE Relays 0 0xFFFFFFFF 1 FC198 0 1
63521 0x5BE0 Events 0 1 1 FC126 1 1
63522 0x5BE1 Targets 0 2 1 FC101 1 1
Short Circuit
63640 0x5C57 Name 0 65535 1 F60_26 Short
Circuit
26
63666 0x5C71 Function 0 4 1 FC100 0 1
63667 0x5C72 Pickup 100 3000 1 x CT F2 600 1
63668 0x5C73 Pickup Delay 0 18000 1 s F2 100 1
63669 0x5C74 Dropout Delay 0 18000 1 s F2 100 1
63670 0x5C75 Relays 0 0xFFFFFFFF 1 FC198 0 1
63672 0x5C77 Block 0 0xFFFFFFFF 1 FC142 0 1
63674 0x5C79 Events 0 1 1 FC126 1 1
63675 0x5C7A Targets 0 2 1 FC101 1 1
Ground Fault
63690 0x5C89 Name 0 65535 1 F60_26 GndFault 26
63703 0x5C96 Trip Function 0 4 1 FC100D 0 1
63704 0x5C97 Ground CT Type 2 6 1 FC104A 6 1
63705 0x5C98 Trip Pickup 1 1000 1 x CT F2 10 1
63706 0x5C99 Trip Pickup 50 1500 1 A F2 1000 1
63707 0x5C9A Trip Pickup Start Delay 0 18000 1 s F2 100 1
63708 0x5C9B Trip Pickup Run Delay 0 18000 1 s F2 100 1
63709 0x5C9C Trip Dropout Delay 0 18000 1 s F2 100 1
63710 0x5C9D Trip Relays 0 0xFFFFFFFF 1 FC198D 0 1
63712 0x5C9F Alarm Function 0 3 1 FC100E 0 1
63713 0x5CA0 Alarm Pickup 1 1000 1 x CT F2 20 1
63714 0x5CA1 Alarm Pickup 50 1500 1 A F2 500 1
63715 0x5CA2 Alarm Pickup Delay 0 18000 1 s F2 100 1
63716 0x5CA3 Alarm Dropout Delay 0 18000 1 s F2 100 1
63717 0x5CA4 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 1
63719 0x5CA6 Block 0 0xFFFFFFFF 1 FC142 0 1
63721 0x5CA8 Events 0 1 1 FC126 1 1
63722 0x5CA9 Targets 0 2 1 FC101 1 1
Acceleration Time
63740 0x5CBB Name 0 65535 1 F60_26 Motor Accel 26
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words