CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 11-123
66299 0x66BA Name 0 65535 1 F60_26 Ph OV 2 26
66312 0x66C7 Function 0 4 1 FC100 0 1
66315 0x66CA Mode 0 1 1 FC260 0 1
66316 0x66CB Pickup 2 300 1 x VT F2 150 1
66317 0x66CC Phases for Operation 0 2 1 FC261 0 1
66318 0x66CD Pickup Delay 0 6000000 1 s F13 1000 1
66320 0x66CF Dropout Delay 0 6000000 1 s F13 1000 1
66322 0x66D1 Relays 0 0xFFFFFFFF 1 FC198 0 1
66324 0x66D3 Block 0 0xFFFFFFFF 1 FC142 0 1
66326 0x66D5 Events 0 1 1 FC126 1 1
66327 0x66D6 Targets 0 2 1 FC101 1 1
Aux OV 1
66350 0x66ED Name 0 65535 1 F60_26 Aux OV 1 26
66363 0x66FA Function 0 4 1 FC100 0 1
66366 0x66FD Pickup 0 300 1 x VT F2 150 1
66367 0x66FE Pickup Delay 0 6000000 1 s F13 1000 1
66369 0x6700 Dropout Delay 0 6000000 1 s F13 1000 1
66371 0x6702 Relays 0 0xFFFFFFFF 1 FC198 0 1
66373 0x6704 Block 0 0xFFFFFFFF 1 FC142 0 1
66375 0x6706 Events 0 1 1 FC126 1 1
66376 0x6707 Targets 0 2 1 FC101 1 1
Aux OV 2
66387 0x6712 Name 0 65535 1 F60_26 Aux OV 2 26
66400 0x671F Function 0 4 1 FC100 0 1
66403 0x6722 Pickup 0 300 1 x VT F2 150 1
66404 0x6723 Pickup Delay 0 6000000 1 s F13 1000 1
66406 0x6725 Dropout Delay 0 6000000 1 s F13 1000 1
66408 0x6727 Relays 0 0xFFFFFFFF 1 FC198 0 1
66410 0x6729 Block 0 0xFFFFFFFF 1 FC142 0 1
66412 0x672B Events 0 1 1 FC126 1 1
66413 0x672C Targets 0 2 1 FC101 1 1
Neutral OverVoltage 1
66440 0x6747 Name 0 65535 1 F60_26 Ntrl OV 1 26
66453 0x6754 Function 0 4 1 FC100 0 1
66456 0x6757 Pickup 2 300 1 x VT F2 30 1
66457 0x6758 Curves 7 19 1 FC161A 7 1
66458 0x6759 Pickup Delay 0 6000000 1 s F13 1000 1
66460 0x675B Dropout Delay 0 6000000 1 s F13 1000 1
66462 0x675D Relays 0 0xFFFFFFFF 1 FC198 0 1
66464 0x675F Block 0 0xFFFFFFFF 1 FC142 0 1
66466 0x6761 Events 0 1 1 FC126 1 1
66467 0x6762 Targets 0 2 1 FC101 1 1
Negative Sequence OverVoltage 1
66530 0x67A1 Name 0 65535 1 F60_26 NegSeq OV
1
26
66543 0x67AE Function 0 4 1 FC100 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words