11-126 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
67190 0x6A35 Minimum Voltage 0 1250 1 x VT F13 700 1
67192 0x6A37 Minimum Current 0 30000 1 x CT F13 200 1
67194 0x6A39 Relays 0 0xFFFFFFFF 1 FC198 0 1
67196 0x6A3B Block 0 0xFFFFFFFF 1 FC142 0 1
67198 0x6A3D Events 0 1 1 FC126 1 1
67199 0x6A3E Targets 0 2 1 FC101 1 1
Underfrequency 6
67210 0x6A49 Name 0 65535 1 F60_26 Underfreq 6 26
67223 0x6A56 Function 0 4 1 FC100 0 1
67224 0x6A57 Signal Input 0x12 0x22 1 FC103A 0x12 1
67225 0x6A58 Pickup 2000 6500 1 Hz F2 5900 1
67226 0x6A59 Pickup Delay 0 6000000 1 s F13 2000 1
67228 0x6A5B Dropout Delay 0 6000000 1 s F13 2000 1
67230 0x6A5D Minimum Voltage 0 1250 1 x VT F13 700 1
67232 0x6A5F Minimum Current 0 30000 1 x CT F13 200 1
67234 0x6A61 Relays 0 0xFFFFFFFF 1 FC198 0 1
67236 0x6A63 Block 0 0xFFFFFFFF 1 FC142 0 1
67238 0x6A65 Events 0 1 1 FC126 1 1
67239 0x6A66 Targets 0 2 1 FC101 1 1
Overfrequency 1
67260 0x6A7B Name 0 65535 1 F60_26 Overfreq 1 26
67273 0x6A88 Function 0 4 1 FC100 0 1
67274 0x6A89 Signal Input 0x12 0x22 1 FC103A 0x12 1
67275 0x6A8A Pickup 2000 6500 1 Hz F2 6050 1
67276 0x6A8B Pickup Delay 0 6000000 1 s F13 5000 1
67278 0x6A8D Dropout Delay 0 6000000 1 s F13 5000 1
67280 0x6A8F Minimum Voltage 0 1250 1 x VT F13 300 1
67282 0x6A91 Relays 0 0xFFFFFFFF 1 FC198 0 1
67284 0x6A93 Block 0 0xFFFFFFFF 1 FC142 0 1
67286 0x6A95 Events 0 1 1 FC126 1 1
67287 0x6A96 Targets 0 2 1 FC101 1 1
Overfrequency 2
67298 0x6AA1 Name 0 65535 1 F60_26 Overfreq 2 26
67311 0x6AAE Function 0 4 1 FC100 0 1
67312 0x6AAF Signal Input 0x12 0x22 1 FC103A 0x12 1
67313 0x6AB0 Pickup 2000 6500 1 Hz F2 6050 1
67314 0x6AB1 Pickup Delay 0 6000000 1 s F13 5000 1
67316 0x6AB3 Dropout Delay 0 6000000 1 s F13 5000 1
67318 0x6AB5 Minimum Voltage 0 1250 1 x VT F13 300 1
67320 0x6AB7 Relays 0 0xFFFFFFFF 1 FC198 0 1
67322 0x6AB9 Block 0 0xFFFFFFFF 1 FC142 0 1
67324 0x6ABB Events 0 1 1 FC126 1 1
67325 0x6ABC Targets 0 2 1 FC101 1 1
Overfrequency 3
67336 0x6AC7 Name 0 65535 1 F60_26 Overfreq 3 26
67349 0x6AD4 Function 0 4 1 FC100 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words