AF-650 GP 3-phase Recommended fuse size Recommended max fuse
[kW] / [HP]
0.25 / 0.33
gG-16 gG-25
0.37 / 0.5
0.75 / 1
1.5 / 2
2.2 / 3
3.7 / 5 gG-20 gG-32
5.5 / 7.5 gG-50 gG-63
7.5 / 10
gG-80 gG-12511 / 15
15 / 20
18.5 / 25 gG-125 gG-150
22 / 30 aR-160 aR-160
30 / 40 aR-200 aR-200
37 / 50 aR-250 aR-250
Table 9.1 200–240V. IP20 / Open Chassis
AF-650 GP 3-phase Recommended fuse size Recommended max fuse
[kW] / [HP]
0.25 / 0.33
gG-20 gG-32
0.37 / 0.5
0.75 / 1
1.5 / 2
2.2 / 3
3.7 / 5
5.5 / 7.5
gG-63 gG-80
7.5 / 10
11 / 15 gG-80 gG-100
15 / 20
gG-125 gG-160
18.5 / 25
22 / 30 aR-160 aR-160
30 / 40 aR-200 aR-200
37 / 50 aR-250 aR-250
Table 9.2 200–240V. IP55 / Nema 12 and IP66 / Nema 4