AF-650 GP
Bussmann PN Alternate External
Siba PN
Alternate External
Ferraz-Shawmut PN
[kW] / [HP] Type JFHR2 Type JFHR2
90 / 125 170M3017 2061032,315 6.9URD30D08A0315
110 / 150 170M3018 2061032,35 6.9URD30D08A0350
132 / 200 170M4011 2061032,35 6.9URD30D08A0350
160 / 250 170M4012 2061032,4 6.9URD30D08A0400
200 / 300 170M4014 2061032,5 6.9URD30D08A0500
250 / 350 170M5011 2062032,55 6.9URD32D08A0550
315 / 400 170M4017 20 610 32.700 6.9URD31D08A0700
335 / 450 170M4017 20 610 32.700 6.9URD31D08A0700
355 / 500 170M6013 22 610 32.900 6.9URD33D08A0900
415 / 600 170M6013 22 610 32.900 6.9URD33D08A0900
500 / 650 170M7081
560 / 750 170M7081
710 / 950 170M7081
785 / 1050 170M7081
800 / 1150 170M7082
1000 / 1350 170M7083
Table 9.19 525–690V, above 125 HP
AF-650 GP Bussmann PN Rating Alternate Siba PN
[kW] / [HP]
630 / 900 170M8611 1100A, 1000V 20 781 32.1000
710 / 1000 170M8611 1100A, 1000V 20 781 32.1000
800 / 1150 170M8611 1100A, 1000V 20 781 32.1000
900 / 1250 170M8611 1100A, 1000V 20 781 32.1000
1000 / 1350 170M8611 1100A, 1000V 20 781 32.1000
1200 / 1600 170M8611 1100A, 1000V 20 781 32.1000
Table 9.20 525–690V, 900 HP and above
*170M fuses from Bussmann shown use the -/80 visual indicator; -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and
amperage may be substituted for external use
**Any minimum 500V UL listed fuse with associated current rating may be used to meet UL requirements.