AN-40 Terminal X30/12 Low Voltage
Range: Function:
0.07 V* [0.00 - par. AN-41 V] Sets the analog input scaling value to correspond to the low reference/feedback value set in par.
AN-44 Term. X30/12 Low Ref./Feedb. Value.
AN-41 Terminal X30/12 High Voltage
Range: Function:
10.00 V* [par. AN-40 - 10.00 V] Sets the analog input scaling value to correspond to the high reference/feedback value set in par.
AN-45 Term. X30/12 High Ref./Feedb. Value.
AN-44 Term. X30/12 Low Ref./Feedb. Value
Range: Function:
0.000 Unit* [-1000000.000 to par. AN-45] Sets the analog output scaling value to correspond to the low voltage value set in par. AN-40 Terminal
X30/12 Low Voltage.
AN-45 Term. X30/12 High Ref./Feedb. Value
Range: Function:
1500.000* [Par. AN-44 to 100000.000] Sets the analog input scaling value to correspond to the high voltage value set in par. AN-41 Terminal
X30/12 High Voltage.
AN-46 Term. X30/12 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing electrical noise on terminal X30/12.
par. AN-46 Term. X30/12 Filter Time Constant cannot be changed while the motor is running.
3.8.6 AN-5# Analog Output 42
Parameters to configure the scaling and limits for Analog Output 1 (terminal 42)
AN-50 Terminal 42 Output
Option: Function:
Select the function of Terminal 42 as an analog current output. Depending on the selection the output is
either a 0-20 mA or 4-20 mA output. The current value can be read out in Keypad in par. DR-65 Analog
Output 42 [mA].
[0] * No operation When no signal on the analog output.
[100] Output frequency 0 Hz = 0 mA; 100 Hz = 20 mA.
[101] Reference par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[102] Feedback par. F-50 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
par. F-50 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
[103] Motor Current Motor current 0 - 20 mA: Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160%
current) is equal to 20 mA.
[104] Torque rel to limit The torque setting is related to setting in par. F-40 Torque Limiter (Driving)
[105] Torq relate to rated The torque is related to the motor torque setting.
[106] Power Taken from par. P-07 Motor Power [kW].
[107] Speed Taken from par. F-53 Maximum Reference. 20 mA = value in par. F-53 Maximum Reference
[108] Torque Torque reference related to 160% torque.
[109] Max Out Freq In relation to par. F-03 Max Output Frequency 1.