PB-23 Parameters for Signals
Array [1000]
Read only
Option: Function:
This parameter contains a list of signals available for selection in par. PB-15 PCD Write Configuration and
par. PB-16 PCD Read Configuration.
PB-27 Parameter Edit
Option: Function:
Parameters can be edited via Profibus, the standard RS485 interface, or the Keypad.
[0] Disabled Disables editing via Profibus.
[1] * Enabled Enables editing via Profibus.
PB-28 Process Control
Option: Function:
Process control (setting of Control Word, speed reference, and process data) is possible via either Profibus
or standard Network but not both simultaneously. Local control is always possible via the Keypad. Control
via process control is possible via either terminals or Network depending on the settings in par.
O-50 Coasting Select to par. O-56 Preset Reference Select.
[0] Disable Disables process control via Profibus, and enables process control via standard Network or Profibus
Master class 2.
[1] * Enable cyclic master Enables process control via Profibus Master Class 1, and disables process control via standard Network
or Profibus Master class 2.
PB-44 Fault Message Counter
Range: Function:
0* [0 - 65535] This parameter displays the number of error events stored in par. PB-45 Fault Code and par. PB-47 Fault
Number. The maximum buffer capacity is eight error events. The buffer and counter are set to 0 upon
reset or power-up.
PB-45 Fault Code
Range: Function:
0* [] This buffer contains the alarm word for all alarms and warnings that have occurred since last reset or
power-up. The maximum buffer capacity is eight error events.
PB-47 Fault Number
Range: Function:
0* [] This buffer contains the alarm number (e.g. 2 for live zero error, 4 for mains phase loss) for all alarms and
warnings that have occurred since last reset or power-up. The maximum buffer capacity is eight error
events.
PB-52 Fault Situation Counter
Range: Function:
0* [0 - 1000] This parameter displays the number of error events which have occurred since last reset of power-up.
PB-53 Profibus Warning Word
Range: Function:
0* []
Read only