Preset ramp bit 1 0
Ramp 1 0 0
Ramp 2 01
Ramp 3 1 0
Ramp 4 11
[36] Mains failure inverse Activates par. SP-10 Line failure. Mains failure inverse is active in the Logic .0. situation.
[41] Latched Precise Stop inverse Sends a latched stop signal when the precise stop function is activated in par. H-83 Precise Stop Func-
tion. The Latched Precise stop inverse function is available for terminals 18 or 19.
[55] DigiPot Increase INCREASE signal to the Digital Potentiometer function described in parameter group F-9#
[56] DigiPot Decrease DECREASE signal to the Digital Potentiometer function described in parameter group F-9#
[57] DigiPot Clear Clears the Digital Potentiometer reference described in parameter group F-9#
[60] Counter A (Terminal 29 or 33 only) Input for increment counting in the LC counter.
[61] Counter A (Terminal 29 or 33 only) Input for decrement counting in the LC counter.
[62] Reset Counter A Input for reset of counter A.
[63] Counter B (Terminal 29 or 33 only) Input for increment counting in the LC counter.
[64] Counter B (Terminal 29 or 33 only) Input for decrement counting in the LC counter.
[65] Reset Counter B Input for reset of counter B.
[70] Mech. Brake Feedback Brake feedback for hoisting applications
[71] Mech. Brake Feedback inv. Inverted brake feedback for hoisting applications
[80] PTC Card 1 All Digital Inputs can be set to PTC Card 1 [80]. However, only one Digital Input must be set to this choice.
E-51 Terminal 27 Mode
Option: Function:
[0] * Input Defines terminal 27 as a digital input.
[1] Output Defines terminal 27 as a digital output.
Please not that this parameter cannot be adjusted while the motor is running.
E-52 Terminal 29 Mode
Option: Function:
[0] * Input Defines terminal 29 as a digital input.
[1] Output Defines terminal 29 as a digital output.
This parameter cannot be adjusted while the motor is running.
E-53 Terminal X30/2 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module OPCGPIO General Purpose I/O Option Module is installed in
the frequency converter.
[1] Reset
[2] Coast inverse
[3] Coast and reset inv
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse