3.6.2 P-2# Motor Selection
Parameters to configure the drive to work with Asynchronous AC Motor or Permanent Magnet Motor
P-20 Motor Construction
Option: Function:
Select the motor construction type.
[0] * Asynchron For asynchronous motors.
[1] PM, non salient SPM
Motor construction can either be asynchronous or permanent magnet (PM) motor.
3.6.3 P-3# Adv. Motor Data
Parameters to configure advanced motor data to the drive.
P-30 Stator Resistance (Rs)
Range: Function:
1.4000
Ohm*
[0.0140 - 140.0000 Ohm] Set the stator resistance value. Enter the value from a motor data sheet or perform an Auto Tune on a
cold motor.
P-31 Rotor Resistance (Rr)
Range: Function:
1.0000
Ohm*
[0.0100 - 100.0000 Ohm] Fine-tuning R
r
will improve shaft performance. Set the rotor resistance value using one of these methods:
1. Run an Auto Tune on a cold motor. The frequency converter will measure the value from the
motor. All compensations are reset to 100%.
2. Enter the R
r
value manually. Obtain the value from the motor supplier.
3. Use the R
r
default setting. The frequency converter establishes the setting on the basis of the
motor nameplate data.
P-33 Stator Leakage Reactance (X1)
Range: Function:
4.0000
Ohm*
[0.0400 - 400.0000 Ohm] Set the stator leakage reactance of the motor using one of these methods:
1. Run an Auto Tune on a cold motor. The frequency converter will measure the value from the
motor.
2. Enter the X
1
value manually. Obtain the value from the motor supplier.
3. Use the X
1
default setting. The frequency converter establishes the setting on the basis of the
motor name plate data.
P-34 Rotor Leakage Reactance (X2)
Range: Function:
4.0000
Ohm*
[0.0400 - 400.0000 Ohm] Set the rotor leakage reactance of the motor using one of these methods:
1. Run an Auto Tune on a cold motor. The frequency converter will measure the value from the
motor.
2. Enter the X
2
value manually. Obtain the value from the motor supplier.
3. Use the X
2
default setting. The frequency converter establishes the setting on the basis of the
motor name plate data.
AF-650 GP Programming Guide
86