Mains Supply 3 x 525- 690 VAC
AF-650 GP 350 HP 400 HP 500 HP
Heavy Duty/Light Duty* HD
LD HD LD HD LD
Typical Shaft output at 550 V [kW] 200 250 250 315 315 355
Typical Shaft output at 575 V [HP] 300 350 350 400 400 450
Typical Shaft output at 690 V [kW] 250 315 315 400 355 450
IP21/Nema 1 Drive Type
42 42 51
IP54/Nema 12 Drive Type 42 42 51
IP00 Open Chassis Drive Type 44 44 52
Output current
Continuous
(at 550 V) [A]
303 360 360 418 395 470
Intermittent (60 sec overload)
(at 550 V) [A]
455 396 540 460 593 517
Continuous
(at 575/ 690 V) [A]
290 344 344 400 380 450
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
435 378 516 440 570 495
Continuous KVA
(at 550 V) [KVA]
289 343 343 398 376 448
Continuous KVA
(at 575 V) [KVA]
289 343 343 398 378 448
Continuous KVA
(at 690 V) [KVA]
347 411 411 478 454 538
Max. input current
Continuous
(at 550 V ) [A]
299 355 355 408 381 453
Continuous
(at 575 V) [A]
286 339 339 390 366 434
Continuous
(at 690 V) [A]
296 352 352 400 366 434
Max. cable size, mains, motor and
load share [mm
2
(AWG)]
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
4 x 240
(4 x 500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 150
(2 x 300 mcm)
2 x 150
(2 x 300 mcm)
2 x 185
(2 x 350 mcm)
Max. external mains fuses [A]
1
500 550 700
Estimated power loss
at 600 V [W]
4)
4601 5493 4938 5852 5107 6132
Estimated power loss
at 690 V [W]
4)
4875 5821 5185 6149 5383 6449
Weight,
Unit Size IP21, IP 54 [kg]
151 165 263
Weight,
Unit Size IP00 [kg]
138 151 221
Efficiency
4)
0.98
Output frequency 0 - 600 Hz 0 - 500 Hz 0 - 500 Hz
Heatsink overtemp. trip 110 °C 110 °C 85 °C
Power card ambient trip 60 °C 60 °C 68 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
AF-650 GP Design Guide
67
4