Mains Supply 3 x 525- 690 VAC
AF-650 GP 550 HP 650 HP 750 HP
Heavy Duty/Light Duty* HD
LD HD LD HD LD
Typical Shaft output at 550 V [kW] 315 400 400 450 450 500
Typical Shaft output at 575 V [HP] 400 500 500 600 600 650
Typical Shaft output at 690 V [kW] 400 500 500 560 560 630
IP21/Nema 1 Drive Type
51 51 51
IP54/Nema Drive Type 51 51 51
IP00 Open Chassis Drive Type 52 52 52
Output current
Continuous
(at 550 V) [A]
429 523 523 596 596 630
Intermittent (60 sec overload)
(at 550 V) [A]
644 575 785 656 894 693
Continuous
(at 575/ 690 V) [A]
410 500 500 570 570 630
Intermittent (60 sec overload)
(at 575/ 690 V) [A]
615 550 750 627 855 693
Continuous KVA
(at 550 V) [KVA]
409 498 498 568 568 600
Continuous KVA
(at 575 V) [KVA]
408 498 498 568 568 627
Continuous KVA
(at 690 V) [KVA]
490 598 598 681 681 753
Max. input current
Continuous
(at 550 V ) [A]
413 504 504 574 574 607
Continuous
(at 575 V) [A]
395 482 482 549 549 607
Continuous
(at 690 V) [A]
395 482 482 549 549 607
Max. cable size, mains, motor and
load share [mm
2
(AWG)]
4x240 (4x500 mcm) 4x240 (4x500 mcm) 4x240 (4x500 mcm)
Max. cable size, brake [mm
2
(AWG)]
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external mains fuses [A]
1
700 900 900
Estimated power loss
at 600 V [W]
4)
5538 6903 7336 8343 8331 9244
Estimated power loss
at 690 V [W]
4)
5818 7249 7671 8727 8715 9673
Weight,
Unit Size IP21, IP 54 [kg]
263 272 313
Weight,
Unit Size IP00 [kg]
221 236 277
Efficiency
4)
0.98
Output frequency 0 - 500 Hz
Heatsink overtemp. trip 85 °C
Power card ambient trip 68 °C
* Heavy Duty = 160% torque during 60 s, Light Duty = 110% torque during 60 s
AF-650 GP Design Guide
68
4

Table of Contents