CE Mark Compliance B-1
September 2004
Introduction For CE Mark compliance, the Model AT868 flow transmitter must
meet both the EMC and LVD directives.
IMPORTANT: CE Mark compliance is required only for units
intended for use in EEC countries.
EMC Compliance For EMC compliance, the electrical connections must be shielded and
grounded as in Table B-1 below. Also refer to Figures B-1 and B-2 on
the next page for illustrations of wiring. After all the necessary
electrical connections have been made, seal any unused cable entry
holes with standard conduit plugs or equivalent.
Note: If the instructions in this appendix are followed, the unit will
comply with the EMC Directive 89/336/EEC.
Table B-1: Wiring Modifications
Connection Cable Type
Termination
Modification
Transducer
RG62 a/u Add metallic cable
clamp from braid to
chassis ground.
Armored RG62 a/u or
conduit
Terminate RG62 a/u
shield to chassis
ground.
Input/Output
22 AWG Shield
(e.g. Baystate #78-1197)
Terminate shield to
chassis ground at the
AT868.
Armored conduit None - grounded via
cable gland.
Power
14 AWG, 3 conductor,
shielded
(e.g. Belden #19364)
Terminate shield to
chassis ground at the
AT868.
Armored Conduit None - grounded via
cable gland.
Shielding
Wires enclosed in a properly-grounded metal con-
duit do not require additional shielding.