3-68 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.34 Loss of excitation (LosExc)
This element is instantiated in the following products: G30, G60.
Table 3-62: Loss of excitation data objects
Table 3-63: Loss of excitation stage 1 objects
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: LosExtPDIS1 LDevice inst: Prot UR element: LOSS OF EXCITATION core functions
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD LOSS EXCIT PKP operand, which becomes
On when either stage 1 or stage 2 of this
element has picked up.
R
general BOOLEAN ST LOSS EXCIT PKP R
dirGeneral ENUMERATED ST 0 R
Op ACT LOSS EXCIT OP operand R
general BOOLEAN ST LOSS EXCIT OP R
Dpo SPS LOSS EXCIT DPO operand R
stVal BOOLEAN ST LOSS EXCIT DPO R
BlkRefγ ORG LOSS OF EXCIT BLK setting for setting
group γ.
R
GEORG R
setSrcRef ObjectReference SP LOSS OF EXCIT BLK for group γ. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting LOSS
OF EXCIT BLK for setting group γ.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: LosExt1PDIS1 LDevice inst: Prot UR element: Loss of Excitation element stage 1 functions
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD LOSS EXCIT STG1 PKP operand R
LNName: LodEncPDIS1 LDevice inst: Prot UR element: LOAD ENCROACHMENT functions