3-70 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.37 Motor thermal model (MotThm)
This element is instantiated in the following products: M60.
Table 3-67: Thermal model data objects
stVal BOOLEAN ST MOTOR ACCEL TIME DPO R
BlkRefγ ORG ACCELERATION BLOCK setting. R
setSrcRef ObjectReference SP ACCELERATION BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
StrAccTmζ MV START ζ ACCELERATION TIME in Sec R
instMag AnalogueValue MX R
instMag.f FLOAT32 START ζ ACCELERATION TIME R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MAccTmPMSS1.StrAccTmζ.db R/W/C
zeroDb INT32 CF 0 R
StrEffAζ MV START ζ EFFECTIVE CURRENT in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 START ζ EFFECTIVE CURRENT R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimension less R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MAccTmPMSS1.StrEffAζ.db R/W/C
zeroDb INT32 CF 0 R
StrPeakAζ MV START ζ PEAK CURRENT in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 START ζ PEAK CURRENT R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MAccTmPMSS1.StrPeakAζ.db R/W/C
zeroDb INT32 CF 0 R
StrTDζ INS START ζ TIME/DATE actual value R
stVal INT32 ST START ζ TIME/DATE actual value R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for time R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
LNName: MotThmPTTR1 LDevice inst: Prot UR element: THERMAL MODEL element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT MOTOR THERMAL OP operand R
general BOOLEAN ST MOTOR THERMAL OP R
Str ACD MOTOR THERMAL PKP operand R
LNName: MAccTmPMSS1 LDevice inst: Prot UR element: Acceleration Time element
data obj. data attribute Type FC UR Name Description R/W/C