CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-71
3
general BOOLEAN ST MOTOR THERMAL PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Dpo SPS MOTOR THERMAL DPO operands R
stVal BOOLEAN ST MOTOR THERMAL DPO R
InRef10 ORG MOTOR OFFLINE setting R
setSrcRef ObjectReference SP MOTOR OFFLINE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef20 ORG EMERGENCY RESTART setting R
setSrcRef ObjectReference SP EMERGENCY RESTART setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef30 ORG SPEED2 MOTOR SWITCH setting R
setSrcRef ObjectReference SP SPEED2 MOTOR SWITCH setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef4γ ORG VD VOLTAGE LOSS setting for setting
group γ.
R
setSrcRef ObjectReference SP VD VOLTAGE LOSS reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef5γ ORG SPEED2 VD VOLTAGE LOSS setting for
setting group γ.
R
setSrcRef ObjectReference SP SPEED2 VD VOLTAGE LOSS
setting
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG THERMAL MODEL BLOCK setting for
setting group γ.
R
setSrcRef ObjectReference SP THERMAL MODEL BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
Restart SPS MOTOR RESTART operand R
stVal BOOLEAN ST MOTOR RESTART R
Offline SPS MOTOR OFFLINE operand R
stVal BOOLEAN ST MOTOR OFFLINE R
Starting SPS MOTOR STARTING operand R
stVal BOOLEAN ST MOTOR STARTING R
Running SPS MOTOR RUNNING operand R
stVal BOOLEAN ST MOTOR RUNNING R
AlmThm SPS MOTOR OVERLOAD operand R
stVal BOOLEAN ST MOTOR OVERLOAD R
StrInh SPS MOTOR START INHIBIT operand R
stVal BOOLEAN ST MOTOR START INHIBIT R
MotStatus ENS Thermal Model MOTOR STATUS R
stVal ENUMERATED ST actual value for Thermal Model
MOTOR STATUS
R
Amp MV THERMAL MODEL LOAD in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 THERMAL MODEL LOAD R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MotThmPTTR1.Amp.db R/W/C
zeroDb INT32 CF 0 R
LNName: MotThmPTTR1 LDevice inst: Prot UR element: THERMAL MODEL element
data obj. data attribute Type FC UR Name Description R/W/C