EasyManua.ls Logo

GE b30 - Page 310

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-72 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
OvlTripTm MV ESTIMATED TRIP TIME ON OVERLOAD in
seconds
R
instMag AnalogueValue MX R
instMag.f FLOAT32 ESTIMATED TRIP TIME ON
OVERLOAD
R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MotThmPTTR1.OvlTripTm.db R/W/C
zeroDb INT32 CF 0 R
ThmCap MV MOTOR THERMAL CAPACITY USED in
percentage (%)
R
instMag AnalogueValue MX R
instMag.f FLOAT32 MOTOR THERMAL CAPACITY
USED
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED -2 is code for percent R
db INT32 CF MotThmPTTR1.ThmCap.db R/W/C
zeroDb INT32 CF 0 R
ThmLOTm MV THERMAL LOCKOUT TIME in seconds R
instMag AnalogueValue MX R
instMag.f FLOAT32 THERMAL LOCKOUT TIME R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec)NOTE: Modbus
measures this value in Minute
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MotThmPTTR1.ThmLOTm.db R/W/C
zeroDb INT32 CF 0 R
MotUnb MV THERMAL MODEL MOTOR UNBALANCE in
percentage (%)
R
instMag AnalogueValue MX R
instMag.f FLOAT32 THERMAL MODEL MOTOR
UNBALANCE
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED -2 is code for percent R
db INT32 CF MotThmPTTR1.MotUnb.db R/W/C
zeroDb INT32 CF 0 R
BiasMotLo
d
MV THERMAL MODEL BIASED MOTOR LOAD in
x FLA
R
instMag AnalogueValue MX R
instMag.f FLOAT32 THERMAL MODEL BIASED
MOTOR LOAD
R
mag Analogue Value MX R
LNName: MotThmPTTR1 LDevice inst: Prot UR element: THERMAL MODEL element
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals