CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-79
3
3.5.2.48 Open pole detector (OpnPl)
This element is instantiated in the following products: C60, D60, L60, L90. It does not apply to open pole detector supervisor
N60.
Table 3-80: Open pole detector data objects
Table 3-81: Open pole detector data objects
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD NTRL VOLT # STG$ PKP operand ”. R
general BOOLEAN ST NTRL VOLT # STG$ PKP R
dirGeneral ENUMERATED ST 0 R
Op ACT NTRL VOLT # STG$ OP operand R
general BOOLEAN ST NTRL VOLT # STG$ OP R
BlkRefγ ORG NTRL VOL # BLK STG$ setting for setting
group γ.
R
GEORG R
setSrcRef ObjectReference SP NTRL VOL # BLK STG$ for group
γ
reference to the data attribute to input R/C
VISIBLE
STRING255
SP R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: OpnPl0SCBR1 LDevice inst: Prot UR element: Open Pole Detector element
data obj. data attribute Type FC UR Name Description R/W/C
BlkRef1 ORG OPEN POLE BLOCK setting R
setSrcRef ObjectReference SP OPEN POLE BLOCK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
ColOpn SPS Logical OR of status value of mapped
FlexLogic operands in TRIP PHASE A, TRIP
PHASE B, TRIP PHASE C”.
R
stVal BOOLEAN ST Status of Logical OR condition to
OpnPl1SCBR1.ColOpn,
OpnPl2SCBR1.ColOpn,
OpnPl3SCBR1.ColOpn
R
PlOpn ACT OPEN POLE OP operand R
general BOOLEAN ST OPEN POLE OP R
BlkPhDis SPS OPEN POLE BLK N operand R
stVal BOOLEAN ST OPEN POLE BLK N R
LNName: OpnPlΘSCBR1 LDevice inst: Prot UR element: Open Pole Detector element for ψ and ψτ
data obj. data attribute Type FC UR Name Description R/W/C
ColOpn SPS Status value of mapped settings TRIP ψ R
stVal BOOLEAN ST Status value TRIP ψ setting R
PlOpn ACT OPEN POLE OP ψ operand R
general BOOLEAN ST OPEN POLE OP ψ R
BkrOpnPl ACT OPEN POLE BKR ψ OP operand R
LNName: NuVUn$PTOV# LDevice inst: Prot UR element: Neutral Voltage Unbalance element # stage $
data obj. data attribute Type FC UR Name Description R/W/C