Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-85
3
Table 3-89: Phase comparison negative sequence voltage (excluding FDH) data objects
Table 3-90: Phase comparison negative sequence voltage (for FDH) data objects
Table 3-91: Phase comparison advanced fault detector rate of change of positive sequence current (excluding FDH)
data objects
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
Op ACT 87PC FDH OP operand R
general BOOLEAN ST 87PC FDH OP R
LNName: PhCmp1PTOV1 LDevice inst: Prot UR element: Negative Sequence Voltage element (except FDH element
specifics) as a part of Phase comparison function
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD 87PC V2 FDL OP operand R
general BOOLEAN ST 87PC V2 FDL OP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
BlkRefγ ORG NEG SEQ VOL FD BLK setting of setting
group γ.
R
setSrcRef ObjectReference SP NEG SEQ VOL FD BLK setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PhCmp2PTOV1 LDevice inst: Prot UR element: Negative Sequence Voltage element specific to FDH element
as a part of Phase comparison function
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD 87PC V2 FDH OP operand R
general BOOLEAN ST 87PC V2 FDH OP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
LNName: PhCmp1FXOT1 LDevice inst: Prot UR element: RATE OF CHANGE OF POS SEQ CURRENT element (except FDH
element specifics) as a part of Phase comparison function
data obj. data attribute Type FC UR Name Description R/W/C
BlkRefγ ORG POS SEQ di/dt BLK setting of setting
group γ.
R
setSrcRef ObjectReference SP POS SEQ di/dt BLK setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
StrVal ASG POS SEQ di/dt FDL PICKUP setting R
setMag AnalogueValue SG R
setMag.f FLOAT32 POS SEQ di/dt FDL PICKUP R
units Unit CF R
units.SIUnit ENUMERATED 1 is code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
minVal AnalogueValue CF R
minVal.f FLOAT32 0.01 R
maxVal AnalogueValue CF R
maxVal.f FLOAT32 5.00 R
stepSize AnalogueValue CF R
stepSize.f FLOAT32 0.01 R
Op ACT 87PC di1/dt FDL OP operand R
general BOOLEAN ST 87PC di1/dt FDL OP R
LNName: PhCmp2PDIF1 LDevice inst: Prot UR element: 87PC SCHEME specific to FDH element
data obj. data attribute Type FC UR Name Description R/W/C