3-90 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-101: Phase current unbalance stage objects
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 Cm Iop A R
phsA.cVal Vector MX R
phsA.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsA.units Unit CF R
phsA.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsA.db INT32U CF PhAUnPTOC#.CompAPh.phsA.db R/W/C
phsA.zeroDb INT32U CF 0 R
phsB CMV R
phsB.instCVal Vector MX R
phsB.instCVal.mag
.f
FLOAT32 Cm Iop B R
phsB.cVal Vector MX R
phsB.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsB.units Unit CF R
phsB.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsB.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsB.db INT32U CF PhAUnPTOC#.CompAPh.phsB.db R/W/C
phsB.zeroDb INT32U CF 0 R
phsC CMV R
phsC.instCVal Vector MX R
phsC.instCVal.mag
.f
FLOAT32 Cm Iop C R
phsC.cVal Vector MX R
phsC.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsC.units Unit CF R
phsC.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsC.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsC.db INT32U CF PhAUnPTOC#.CompAPh.phsC.db R/W/C
phsC.zeroDb INT32U CF 0 R
LNName: PhAUn$PTOC# LDevice inst: Prot UR element: Phase Current Unbalance element # Stage $
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD CUR BAL # STG$ PKP operands (including
individual three phases of this stage),
which indicates Op will operate when
delay expires.
R
general BOOLEAN ST Logical OR of data attributes
phsA, phsB and phsC
R
dirGeneral ENUMERATED ST 0, the code for unknown. R
phsA BOOLEAN ST CUR BAL # STG$A PKP R
dirPhsA ENUMERATED ST 0, the code for unknown. R
phsB BOOLEAN ST CUR BAL # STG$B PKP R
dirPhsB ENUMERATED ST 0, the code for unknown. R
phsC BOOLEAN ST CUR BAL # STG$C PKP R
dirPhsC ENUMERATED ST 0, the code for unknown. R
Op ACT CUR BAL # OP operands (including
individual three phases of this stage).
R
LNName: PhAUnPTOC# LDevice inst: Prot UR element: Phase Current Unbalance element #
data obj. data attribute Type FC UR Name Description R/W/C