CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-91
3
3.5.2.56 Phase directional (PhsDir)
This element is instantiated in the following products: B30, C70, D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-102: Phase directional data objects
3.5.2.57 Phase distance (PhsDis)
This element is instantiated in the following products: D30, D60, G60, L60, L90, T60.
Table 3-103: Phase distance data objects
general BOOLEAN ST Logical OR of data attributes
phsA, phsB, phsC
R
phsA BOOLEAN ST CUR BAL # STG$A OP R
phsB BOOLEAN ST CUR BAL # STG$B OP R
phsC BOOLEAN ST CUR BAL # STG$C OP R
BlkRefγ ORG CUR UNBL # BLK STG$ setting for setting
group γ.
R
setSrcRef ObjectReference SP CUR UNBL # BLK STG$ for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PhsDirRDIR# LDevice inst: Prot UR element: Phase Directional element # (ANSI 67P)
data obj. data attribute Type FC UR Name Description R/W/C
Dir ACD PH DIR # BLK operand, which becomes
On when phase current is flowing in the
set direction
R
general BOOLEAN ST PH DIR # BLK R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
phsA BOOLEAN ST PH DIR # BLK A R
dirPhsA ENUMERATED ST 0, the code for unknown R
phsB BOOLEAN ST PH DIR # BLK B R
dirPhsB ENUMERATED ST 0, the code for unknown R
phsC BOOLEAN ST PH DIR # BLK C R
dirPhsC ENUMERATED ST 0, the code for unknown R
BlkRefγ ORG PHASE DIR # BLOCK setting for setting
group γ.
R
setSrcRef ObjectReference SP PHASE DIR # BLOCK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PhsDisPDIS# LDevice inst: Prot UR element: Phase Distance Z# settings
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD PHS DIST Z# PKP operand in Phase-To-
Phase
R
general BOOLEAN ST PH DIST Z# PKP R
dirGeneral ENUMERATED ST 1(Forward) if PHS DIST Z DIR value is
Forward, 2 (backward) if PHS DIST Z1 DIR
value is Reverse, and otherwise 0
(unknown).
R
Op ACT PHS DIST Z# OP operand in Phase-To-
Phase
R
general BOOLEAN ST PHS DIST Z# OP R
StrPhsφ SPS PHS DIST Z# PKP θ operand in Phase-To-
Phase
R
stVal BOOLEAN ST PHS DIST Z# PKP θ R
DpoPhsφ SPS PHS DIST Z# DPO θ operand in Phase-To-
Phase
R
stVal BOOLEAN ST PHS DIST Z# DPO θ R
OpPhsφ SPS PH DIST Z # OP θ operand R
LNName: PhAUn$PTOC# LDevice inst: Prot UR element: Phase Current Unbalance element # Stage $
data obj. data attribute Type FC UR Name Description R/W/C