3-92 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.58 Phase instantaneous overcurrent (PhsIoc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-104: Phase instantaneous overcurrent data objects
3.5.2.59 Phase overvoltage (PhsOv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
stVal BOOLEAN ST PH DIST Z# OP θ R
ASupnφ SPS PHS DIST Z# SUPN θ operand in Phase-
To-Phase
R
stVal BOOLEAN ST PHS DIST Z# SUPN θ R
BlkRefγ ORG PHS DIST Z# BLK setting for setting group
γ.
R
setSrcRef ObjectReference SP PHS DIST Z# BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ2 ORG instantiated only in logical node instance
1
R
setSrcRef ObjectReference SP setting FORCE SELF-POLAR reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRefγ3 ORG instantiated only in logical node instance
1
R
setSrcRef ObjectReference SP setting FORCE MEM-POLAR l reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PhsIocPIOC# LDevice inst: Prot UR element: Phase Instantaneous Overcurrent element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD PHASE IOC# PKP operands (including
individual three phases), which indicates
Op will operate when delay expires
R
general BOOLEAN ST PHASE IOC# PKP R
dirGeneral ENUMERATED ST 0, the code for unknown R
phsA BOOLEAN ST PHASE IOC# PKP A R
dirPhsA ENUMERATED ST 0, the code for unknown R
phsB BOOLEAN ST PHASE IOC# PKP B R
dirPhsB ENUMERATED ST 0, the code for unknown R
phsC BOOLEAN ST PHASE IOC# PKP C R
dirPhsC ENUMERATED ST 0, the code for unknown R
Op ACT PHASE IOC# OP operands (including
individual three phases)
R
general BOOLEAN ST PHASE IOC# OP R
phsA BOOLEAN ST PHASE IOC# OP A R
phsB BOOLEAN ST PHASE IOC# OP B R
phsC BOOLEAN ST PHASE IOC# OP C R
Dpo SPS PHASE IOC# DPO operand R
stVal BOOLEAN ST PHASE IOC# DPO R
DpoPhsβ SPS PHASE IOC# DPO β operands” (where β
refers to Phase-A, B or C)
R
stVal BOOLEAN ST PHASE IOC# DPO β (where β
refers to Phase-A, B or C)
R
BlkRefγβ ORG PHASE IOC# BLOCK β setting for setting
group γ.” (where β refers to Phase-A, B or
C)
R
setSrcRef ObjectReference SP PHASE IOC# BLOCK β (where β
refers to Phase-A, B or C)
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PhsDisPDIS# LDevice inst: Prot UR element: Phase Distance Z# settings
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents