3-120 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
stVal BOOLEAN ST ROTOR ALARM # OP R
BlkRef1 ORG BRB BLOCK setting R
GEORG R
setSrcRef ObjectReference SP BRB BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting BRB
BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
CompLevel MV COMPONENT LEVEL in dB R
instMag AnalogueValue MX R
instMag.f FLOAT32 COMPONENT LEVEL R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded
exception
R
units Unit CF R
units.SIUnit ENUMERATED 79 R
units.multiplier ENUMERATED 0 R
db INT32 CF BknRotSVBR1.CompLevel.db R/W/C
zeroDb INT32 CF 0 R
CompHz MV COMPONENT FREQ. in Hz R
instMag AnalogueValue MX R
instMag.f FLOAT32 COMPONENT FREQ. R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded
exception
R
units Unit CF R
units.SIUnit ENUMERATED 33 R
units.multiplier ENUMERATED 0 R
db INT32 CF BknRotSVBR1.CompHz.db R/W/C
zeroDb INT32 CF 0 R
MotLoad MV MOTOR LOAD AT BRB CALC. in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 MOTOR LOAD AT BRB CALC. R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
db INT32U CF BknRotSVBR1.MotLoad.db R/W/C
zeroDb INT32U CF 0 R
LoadDev MV LOAD DEV. AT BRB CALC. in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 LOAD DEV. AT BRB CALC. R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
LNName: BknRotSVBR1 LDevice inst: Ctrl UR element: Broken Rotor Bar element
data obj. data attribute Type FC UR Name Description R/W/C