3-68 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.32 Line pickup (LinPkp)
This element is instantiated in the following products: D30, D60, L60, L90.
Table 3-59: Line pickup data objects
3.5.2.33 Load encroachment (LodEn)
This element is instantiated in the following products: D30, D60, F60, L60, L90, T60.
phsθ.instCVal Vector MX R
phsθ.instCVal.mag
.f
FLOAT32 TERMINAL 2 Iθ magnitude, in
primary amps
R
phsθ.instCVal.ang
.f
FLOAT32 TERMINAL 2 UR range -180...+180 converted to 0...360R
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 TERMINAL 2 Iθ magnitude, in
primary amps, with deadband
R
phsθ.cVal.ang.f FLOAT32 TERMINAL 2 UR range -180...+180 converted to 0...360R
phsθ.units Unit CF R
phsθ.units.SIUnit ENUMERATED 5, the code for amps R
phsθ.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsθ.db INT32U CF LinDf2MMXU1.A.phsθ.db R/W/C
phsθ.dbAng INT32U CF LinDf2MMXU1.A.phsθ.dbAng R/W/C
phsθ.zeroDb INT32U CF CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
LNName: LinPkpPIOC1 LDevice inst: Prot UR element: Line Pickup functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD LINE PICKUP PKP operand R
general BOOLEAN ST LINE PICKUP PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT LINE PICKUP OP operand R
general BOOLEAN ST LINE PICKUP OP R
Dpo SPS LINE PICKUP DPO operand, which is the
inverse of LINE PICKUP PKP
R
stVal BOOLEAN ST LINE PICKUP DPO R
UnAφ SPS LINE PICKUP operand that activates on
phase θ current below 5% of nominal
R
stVal BOOLEAN ST LINE PICKUP I<θ R
UnV SPS LINE PICKUP UV PKP operand R
stVal BOOLEAN ST LINE PICKUP UV PKP R
LeoSt SPS LINE PICKUP LEO PKP operand R
stVal BOOLEAN ST LINE PICKUP LEO PKP R
Zn2Tr SPS LINE PICKUP RCL TRIP operand R
stVal BOOLEAN ST LINE PICKUP RCL TRIP R
BlkRefγ ORG LINE PICKUP BLOCK setting for setting
group γ.
R
setSrcRef ObjectReference SP LINE PICKUP BLOCK for group γ
. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: LinDf2MMXU1 LDevice inst: Prot UR element: Line Differential element (ANSI 87L) – terminal 2 current
function
data obj. data attribute Type FC UR Name Description R/W/C