CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-71
3
Table 3-64: Mechanical jam data objects
3.5.2.36 Motor acceleration time (MAccTm)
This element is instantiated in the following products: M60.
Table 3-65: Motor acceleration time data objects
LNName: MecJamPMSS1 LDevice inst: Prot UR element: MECHANICAL JAM element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD MECHANICAL JAM PKP operand R
general BOOLEAN ST MECHANICAL JAM PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT MECHANICAL JAM OP operand R
general BOOLEAN ST MECHANICAL JAM OP R
Dpo SPS MECHANICAL JAM DPO operand, which is
the inverse of MECHANICAL JAM PKP
R
stVal BOOLEAN ST MECHANICAL JAM DPO R
BlkRefγ ORG MECH JAM BLK setting for setting group γR
setSrcRef ObjectReference SP MECH JAM BLK for group γ reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: MAccTmPMSS1 LDevice inst: Prot UR element: Acceleration Time element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT MOTOR ACCEL TIME OP operand R
general BOOLEAN ST MOTOR ACCEL TIME OP R
Dpo SPS MOTOR ACCEL TIME DPO operand R
stVal BOOLEAN ST MOTOR ACCEL TIME DPO R
BlkRefγ ORG ACCELERATION BLOCK setting. R
setSrcRef ObjectReference SP ACCELERATION BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
StrAccTmζ MV START ζ ACCELERATION TIME in Sec R
instMag AnalogueValue MX R
instMag.f FLOAT32 START ζ ACCELERATION TIME R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MAccTmPMSS1.StrAccTmζ.db R/W/C
zeroDb INT32 CF 0 R
StrEffAζ MV START ζ EFFECTIVE CURRENT in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 START ζ EFFECTIVE CURRENT R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimension less R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MAccTmPMSS1.StrEffAζ.db R/W/C
zeroDb INT32 CF 0 R
StrPeakAζ MV START ζ PEAK CURRENT in x FLA R