CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-73
3
Restart SPS MOTOR RESTART operand R
stVal BOOLEAN ST MOTOR RESTART R
Offline SPS MOTOR OFFLINE operand R
stVal BOOLEAN ST MOTOR OFFLINE R
Starting SPS MOTOR STARTING operand R
stVal BOOLEAN ST MOTOR STARTING R
Running SPS MOTOR RUNNING operand R
stVal BOOLEAN ST MOTOR RUNNING R
AlmThm SPS MOTOR OVERLOAD operand R
stVal BOOLEAN ST MOTOR OVERLOAD R
StrInh SPS MOTOR START INHIBIT operand R
stVal BOOLEAN ST MOTOR START INHIBIT R
MotStatus ENS Thermal Model MOTOR STATUS R
stVal ENUMERATED ST actual value for Thermal Model
MOTOR STATUS
R
Amp MV THERMAL MODEL LOAD in x FLA R
instMag AnalogueValue MX R
instMag.f FLOAT32 THERMAL MODEL LOAD R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MotThmPTTR1.Amp.db R/W/C
zeroDb INT32 CF 0 R
OvlTripTm MV ESTIMATED TRIP TIME ON OVERLOAD in
seconds
R
instMag AnalogueValue MX R
instMag.f FLOAT32 ESTIMATED TRIP TIME ON
OVERLOAD
R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32 CF MotThmPTTR1.OvlTripTm.db R/W/C
zeroDb INT32 CF 0 R
ThmCap MV MOTOR THERMAL CAPACITY USED in
percentage (%)
R
instMag AnalogueValue MX R
instMag.f FLOAT32 MOTOR THERMAL CAPACITY
USED
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded
exception
R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED -2 is code for percent R
db INT32 CF MotThmPTTR1.ThmCap.db R/W/C
zeroDb INT32 CF 0 R
ThmLOTm MV THERMAL LOCKOUT TIME in seconds R
instMag AnalogueValue MX R
LNName: MotThmPTTR1 LDevice inst: Prot UR element: THERMAL MODEL element
data obj. data attribute Type FC UR Name Description R/W/C