Table 3-78: Neutral voltage unbalance stage objects
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
db INT32U CF NuVUnPTOV#.BusV0.db R/W/C
dbAng INT32U CF NuVUnPTOV#.BusV0.dbAng R/W/C
zeroDb INT32U CF 0 R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
VOp MV NEUTRAL VOLTAGE UNBALANCE # Vop, in
p.u.
R
instMag AnalogueValue MX R
instMag.f FLOAT32 NEUTRAL VOLTAGE UNBALANCE
# Vop
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
db INT32U CF NuVUnPTOV#.VOp.db R/W/C
zeroDb INT32U CF 0 R
VRst MV NEUTRAL VOLTAGE UNBALANCE # Vres, in
p.u.
R
instMag AnalogueValue MX R
instMag.f FLOAT32 NEUTRAL VOLTAGE UNBALANCE
# Vres
R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
db INT32U CF NuVUnPTOV#.VRst.db R/W/C
zeroDb INT32U CF 0 R
LNName: NuVUn$PTOV# LDevice inst: Prot UR element: Neutral Voltage Unbalance element # stage $
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD NTRL VOLT # STG$ PKP operand ”. R
general BOOLEAN ST NTRL VOLT # STG$ PKP R
dirGeneral ENUMERATED ST 0 R
Op ACT NTRL VOLT # STG$ OP operand R
general BOOLEAN ST NTRL VOLT # STG$ OP R
BlkRefγ ORG NTRL VOL # BLK STG$ setting for setting
group γ.
R
GEORG R
setSrcRef ObjectReference SP NTRL VOL # BLK STG$ for group
γ
reference to the data attribute to input R/C
VISIBLE
STRING255
SP R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: NuVUnPTOV# LDevice inst: Prot UR element: Neutral Voltage Unbalance element #
data obj. data attribute Type FC UR Name Description R/W/C