CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-101
3
3.5.2.67 Sensitive directional power (Sen)
This element is instantiated in the following products: C60, D60, F60, G30, G60, L90, M60, N60, T60.
Table 3-112: Sensitive directional power general data objects
stVal BOOLEAN ST RRTD RTD # ALARM OP R
Dpo SPS RRTD RTD # TRIP DPO operand R
stVal BOOLEAN ST RRTD RTD # TRIP DPO R
DpoAlm SPS RRTD RTD # ALARM DPO operand R
stVal BOOLEAN ST RRTD RTD # ALARM DPO R
OpnCirc SPS RRTD RTD # OPEN operand R
stVal BOOLEAN ST RRTD RTD # OPEN R
ShrtCirc SPS RRTD RTD # SHORTED operand R
stVal BOOLEAN ST RRTD RTD # SHORTED R
Tmp MV RRTD INPUT # Temperature in degree
Celsius
R
instMag AnalogueValue MX R
instMag.f FLOAT32 RRTD INPUT # R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 23 R
units.multiplier ENUMERATED 0 R
db INT32U CF RRTDsSTMP#.Tmp.db R/W/C
zeroDb INT32U CF 0 R
BlkRef1 ORG RRTD # BLOCK setting. R
GEORG R
setSrcRef ObjectReference SP RRTD # BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
RRTD # BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: SenPDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # core functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD DIR POWER # PKP operand, which
becomes On when either stage 1 or stage
2 of this element has picked up.
R
general BOOLEAN ST DIR POWER # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT DIR POWER # OP operand R
general BOOLEAN ST DIR POWER # OP R
Dpo SPS DIR POWER # DPO operand, which is the
inverse of DIR POWER OP
R
stVal BOOLEAN ST DIR POWER # DPO R
LNName: RRTDsSTMP# LDevice inst: Prot UR element: RRTD Input #
data obj. data attribute Type FC UR Name Description R/W/C