3-102 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-113: Sensitive directional power stage 1 data objects
Table 3-114: Sensitive directional power stage 2 data objects
3.5.2.68 Speed 2 motor acceleration time (S2AcTm)
This element is instantiated in the following products: M60.
TotW MV DIRECTIONAL POWER # 3-PHASE, in
primary watts
R
instMag AnalogueValue MX R
instMag.f FLOAT32 DIRECTIONAL POWER # 3φ R
mag AnalogueValue MX R
mag.f FLOAT32 DIRECTIONAL POWER # 3φ, deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 38, the code for primary watts (J/s) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF SenPDOP#.TotW.db R/W/C
zeroDb INT32U CF 3-phase power cut-off level in percent
multiplied by 1000
R
BlkRefγ ORG DIR POWER # BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP DIR POWER # BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: Sen1PDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # stage 1 functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD DIR POWER # STG1 PKP operand, which
becomes On when the directional power
comparator has operated.
R
general BOOLEAN ST DIR POWER # STG1 PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT DIR POWER # STG1 OP operand R
general BOOLEAN ST DIR POWER # STG1 OP R
Dpo SPS DIR POWER # STG1 DPO operand, which
is the inverse of DIR POWER STG1 OP
R
stVal BOOLEAN ST DIR POWER # STG1 DPO R
LNName: Sen2PDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # stage 2 functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD DIR POWER # STG2 PKP operand, which
becomes On when the directional power
comparator has operated.
R
general BOOLEAN ST DIR POWER # STG2 PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT DIR POWER # STG2 OP operand R
general BOOLEAN ST DIR POWER # STG2 OP R
Dpo SPS DIR POWER # STG2 DPO operand, which
is the inverse of DIR POWER STG2 OP
R
stVal BOOLEAN ST DIR POWER # STG2 DPO R
LNName: SenPDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # core functions
data obj. data attribute Type FC UR Name Description R/W/C