CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-135
3
3.5.3.19 PID regulator (PIDReg)
This element is instantiated in the following products: C30, F35.
Table 3-156: PID regulator data objects
stVal BOOLEAN ST STARTS-PER-HOUR DPO R
BlkRef ORG STARTS/HR BLK setting. R
GEORG R
setSrcRef ObjectReference SP STARTS/HR BLK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
STARTS/HR BLK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
StrHrLOTm MV Start/Hour Lockout Time in min R
instMag AnalogueValue MX R
instMag.f FLOAT32 Start/Hour Lockout Time R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4 R
units.multiplier ENUMERATED 0 R
db INT32 CF StrRtePMRI1.StrHrLOTm.db R/W/C
zeroDb INT32 CF 0 R
LNName: PIDRegFPID# LDevice inst: Ctrl UR element: PID Regulator element #
data obj. data attribute Type FC UR Name Description R/W/C
Raise SPS PID # RAISE operand value R
stVal BOOLEAN ST PID # RAISE R
Lower SPS PID # LOWER operand value R
stVal BOOLEAN ST PID # LOWER R
Out MV PID # Out value R
instMag AnalogueValue MX R
instMag.f FLOAT32 PID # Out R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF PIDRegFPID#.Out.db R/W/C
zeroDb INT32U CF 0 R
DeltaOut MV PID # Delta Out value R
instMag AnalogueValue MX R
instMag.f FLOAT32 PID # Delta Out R
mag AnalogueValue MX R
LNName: StrRtePMRI1 LDevice inst: Ctrl UR element: Maximum starting rate element
data obj. data attribute Type FC UR Name Description R/W/C